Siemens DC Governor 6RA70 Quick Setup Method

Siemens DC Governor 6RA70 Quick Setup Method

DC governor sometimes need to restore parameters to factory settings or reset parameters in use. What parameters need to be set? The following will briefly describe the 6RA70 rapid setting method: need to set: armature current, excitation current, armature voltage, excitation voltage, feedback mode, given source, starting source, automatic tuning optimization, generally these parameters are sufficient

The DC governor is an all-digital rectifier with three-phase input and armature currents from 15a to 2200a. Compact rectifiers can be used in parallel to provide currents up to 12000a and the excitation circuit can supply up to 85a (this current Depends on the armature rated current)

(1) 6ra70 governor parameter settings and self-tuning debugging settings

P051=21; Restore to factory settings (use this setting if you are not sure which parameters have been modified)

P051=40; Allow modification of parameters

P052=3 ; Show all parameters

P100 = armature rated current (this can be set by referring to the motor nameplate during commissioning)

P101=Armast rated voltage (this can be set by referring to the motor nameplate during commissioning)

P102=excitation rated current (this can be set by referring to the motor nameplate during commissioning)

P104,p105,p106,p107,p108,p109,p114,default

P082=1, the excitation circuit is closed together with the main circuit contactor

P083=3, the speed feedback signal is provided by emf, 1=xt104 xt103 is provided (speed feedback), 2= encoder feedback.

If p083=2 is selected, set the following parameters

P140=1, encoder type 1

P141=1024, encoder pulse number

P142=1, encoder output

P143=3000, setting the maximum operating speed of the motor

If p083=1 is selected, please set the following parameters

P741 = speed feedback generator voltage feedback. Algorithm: For example, the nameplate 110v 2000 speed motor, motor rated speed 1500, then set the p741 voltage is 83v.

Optimized operation: (here we only do current loop optimization)

P051=25 , pre-control of armature and excitation and optimal operation of current regulator start the governor, 6ra70 will automatically run, optimizing current loop and excitation parameters.

Oximeter

Provide you with the supply of pulse oximeter finger. to help you safely get back to your daily routine.

With more than 15+ yrs rich MFG experience, you can definitely trust in and cooperate with.

Our strict quality control protocol thoroughly vets every aspect of production, storage, and shipments all the way way to our end customers.

Our products include pulse Oximeter Finger, Forehead Thermometer, Automatic foam soap dispenser, etc.

Pulse Oximeter Manufacturers, oxygen saturation, oximetry

TOPNOTCH INTERNATIONAL GROUP LIMITED , https://www.itopnoobluetooth.com